A two position DIP switch between the two main connectors, is visible from the connector edge
of the unit. These switches are for future expansion and currently have not effect on the
operation of the unit.
OUTPUTS
The PD100 outputs include a form C relay for reporting OUT conditions and a dc logic output for
reporting no metal within sensing range of the probe.
The logic output is labeled METAL since it provides an indication that the metal target is within
sensing range. The intent of this output is to proximity of the target though it may be outside the
calibrated accept zone. This output provides a dc sourcing signal that switches between zero
volts and 22 volts, delivering up to 100 mA.
The METAL output is ON (sourcing at 22 volts) when material is within sensing range of the
probe.
INDICATORS
The function of the indicators and controls on the PD100 are described in the following
paragraphs:
1. The amber OUT indicator is ON whenever the target is beyond the position threshold
established during calibration.
2. The green OK indicator is ON whenever the target is at or inside the position threshold as
established during calibration.
Through various flashing patterns, these indicators also provide information regarding system
mode (calibrate vs operate), firmware version number, and error conditions. Reading firmware
version is described later in this document. All other flash patterns can be interpreted as follows:
Alternate flashing of amber and green indicates busy such as during initialization after power-up.
Simultaneous flashing of amber and green indicates failed calibration. This error can occur if the
gap between the probe and the target is excessive at calibration.
Green flashing, amber off - calibration in process.
Green flashing, amber on - probe error. Probe may not be connected, probe wire broken, or
probe may be defective.